Reasons for excessive surface temperature of water-cooled condenser

classification:

Industry News


During the working process of the refrigeration system, the temperature of the outer surface of the water-cooled stage condenser should generally be close to room temperature, and it will not feel hot to the touch. Once the surface temperature is found to be too high, the cause should be found out and measures should be taken to eliminate this phenomenon.

Generally speaking, the main cause of the increase in condenser temperature is the problem of cooling water. There are usually the following four situations:

1) The amount of cooling water is insufficient and the water pressure is insufficient. The water-cooled condenser relies on the cooling water to take away the latent heat released when the refrigerant vapor is condensed. Therefore, the cooling water pressure is not enough and the flow rate does not meet the rated requirements, and the heat dissipation capacity is limited, which eventually causes the surface temperature of the condenser to rise.

2) The cooling water temperature is too high, higher than the rated operating temperature (usually 32°C). For cooling water temperature in Vietnam, the smaller the refrigerant cooling temperature difference, the smaller the amount of heat transfer, the refrigerant cannot be effectively cooled, and the surface temperature of the condenser will rise.

3) The poor quality of the cooling water leads to scaling on the inner wall of the cooling water pipe in the condenser and increases the thermal resistance, which affects the heat exchange between the refrigerant and the cooling water and reduces the heat transfer effect. This kind of failure often occurs in equipment that has been used for a long time and is not cleaned regularly. The solution is to remove the scale.

4) Wrong installation of cooling water inlet pipe and outlet pipe. The normal installation position is generally that the inlet pipe is low and the outlet pipe is high, that is, "low inlet and high outlet". If the inlet pipe is set high, the cooling water cannot be completely filled in the condenser, the heat transfer area will be reduced, and the refrigerant vapor will not be effectively condensed, which will increase the surface temperature of the condenser.

When the surface temperature of the condenser increases, it means that the condensing effect is recommended, and the cooling capacity of the system will decrease.