Common faults and troubleshooting methods of refrigeration compressors
classification:
Industry News
The compressor is the heart of the refrigeration system. It sucks in low-temperature and low-pressure refrigerant gas from the suction pipe, drives the piston to compress it through the operation of the motor, and discharges the high-temperature and high-pressure refrigerant liquid to the exhaust pipe to provide power for the refrigeration cycle. So as to realize the refrigeration cycle of compression-condensation-expansion-evaporation (heat absorption).
Now let us look at the common faults and troubleshooting methods of compressors:
1. The compressor stops suddenly during operation:
1. The reasons for the sudden shutdown of the compressor during operation are:
(1) The suction pressure is too low, lower than the low pressure lower limit of the pressure relay;
(2) Exhaust pressure is too high, causing the high-voltage relay to operate and power off;
(3) If the oil pressure is too low, the oil pressure relay will act as a relay;
(4) The motor is overloaded and the thermal relay acts as a relay;
2. How to eliminate the sudden stop of the compressor during operation:
(1) Check the reason. If the pipeline is blocked, the pipeline should be unblocked. If the system refrigerant is insufficient, add it;
(2) Check the cooling capacity or cooling air volume of the condenser;
(3) Check the pipelines and pumps of the oil transportation system;
(4) Check whether the power supply voltage is low or the cooling load is too large;
2. Exhaust gas compression is too high
1. The reasons for excessive exhaust compression are:
(1) The cooling water volume of the water-cooled condenser is insufficient or the cooling air volume of the air-cooled condenser is insufficient;
(2) The surface of the condenser tube cluster is too thick or oily, which causes difficulty in heat dissipation;
(3) There is air in the refrigeration system;
(4) Overfilling of refrigerant;
(5) The valve in the exhaust pipe fails, causing excessive pressure;
2. Elimination method for excessive exhaust compression:
(1) Check whether the valve is fully opened, increase the water supply, or check whether the motor voltage, speed, and transmission belt are too loose;
(2) Wash the scale and brush the oil stains to make the surface of the condenser tube cluster clean;
(3) Release the air;
(4) Exhaust excess refrigerant;
(5) Check and correct the valve;
Three, the wet stroke of the compressor
1. The reasons for the wet stroke of the compressor are:
(1) The thermal expansion valve fails and the opening is too large;
(2) The solenoid valve fails, a large amount of refrigerant enters the evaporator pipe after shutdown, and enters the compressor when it is turned on again;
(3) The system is filled with too much refrigerant;
(4) The temperature sensing bulb of the thermal expansion valve is loose and unbound, which causes the opening of the thermal expansion valve to increase;
2. Elimination method of compressor wet stroke:
(1) Close the liquid supply valve and repair the thermal expansion valve;
(2) Overhaul the solenoid valve;
(3) Release excess refrigerant;
(4) Check the binding of the temperature sensing bag;
Fourth, the compressor is stuck
1. The reasons why the compressor is stuck are:
(1) There are dirty impurities in the lubricating oil;
(2) The oil delivery pipe of the oil pump is blocked, causing the cylinder to run out of oil and the piston is stuck;
(3) The shank pin of the main gear of the oil pump inserted into the crank is twisted, causing the oil system to cut off;
2. Elimination method of compressor jam:
(1) Replace with new lubricating oil;
(2) Check and repair the oil pump pipeline;
(3) Repair and replace the main gear shaft of the oil pump;
Five, there is abnormal sound in the cylinder
1. The reasons for the abnormal sound in the cylinder are:
(1) The dead center clearance in the cylinder is too small;
(2) The clearance between the piston pin and the connecting rod bushing is too large;
(3) The valve disc is broken;
(4) The sound of oil hit by the crankshaft or the big end of the connecting rod;
2. There is abnormal sound in the cylinder
(1) Adjust the thickened cylinder gasket;
(2) Replace the piston pin or bushing;
(3) Shut down immediately to replace the valve;
(4) There is no need to shut down for a short time, such as stopping for inspection after several minutes;
Six, there is sound in the crankcase
1. The reasons for the sound in the crankcase are:
(1) The connecting rod nut is loose;
(2) The gap of the connecting rod head bearing bush is too large;
2. Elimination of sound in the crankcase:
(1) Stop and re-tighten;
(2) Replace the tiles;
Seven, the compressor does not start
1. The reasons why the compressor cannot start are:
(1) Poor contact and blown fuse for power failure;
(2) Poor contact of the vertical contact point of the starter;
(3) The temperature controller is out of adjustment or malfunctions;
(4) The adjustment of the pressure relay is not suitable;
2. The troubleshooting method for the compressor not to start:
(1) Check the power supply and fuse;
(2) Check the starter and clean the contacts with gauze;
(3) Check the position of the temperature indication and check all components;
(4) Check the components or set values of the pressure relay;
8. Insufficient cooling capacity of compressor
1. The reasons for the insufficient cooling capacity of the compressor are:
(1) The piston ring is worn or the gap between the piston and the cylinder is too large due to wear;
2. Elimination methods for insufficient compressor cooling capacity:
(1) Replace with new piston ring or overhaul with new parts;
Nine, the compressor and motor coupling have noise
1. The reasons for the noise of the compressor and motor coupling are:
(1) Improper coordination of compressor and motor coupling;
(2) The key and the keyway of the coupling are not properly matched;
(3) The elastic ring of the coupling is loose or damaged;
(4) The belt is too loose;
(5) The inner hole of the coupling and the shaft fit loosely;
2. Elimination method of noise in the coupling of compressor and motor
(1) Reassemble according to the correct assembly requirements;
(2) Adjust the fit between the key and the keyway, and replace it with a new key;
(3) Tighten the elastic ring or replace with new parts;
(4) Adjust and tighten the belt;
(5) Adjust and tighten the coupling.